(a) Scope. This section provides test procedures, pursuant to the Energy Policy and Conservation Act (EPCA), as amended, which must be followed for measuring the combustion efficiency and/or thermal efficiency of a gas- or oil-fired commercial packaged boiler.

Ask a business law question, get an answer ASAP!
Thousands of highly rated, verified business lawyers.
Click here to chat with a lawyer about your rights.

(b) Testing and Calculations. Determine the thermal efficiency or combustion efficiency of commercial packaged boilers by conducting the appropriate test procedure(s) indicated in Table 1 of this section.

Table 1—Test Requirements for Commercial Packaged Boiler Equipment Classes

Equipment categorySubcategoryCertified rated input
Btu/h
Standards efficiency metric
(§ 431.87)
Test procedure
(corresponding to
standards efficiency
metric required
by § 431.87)
Hot WaterGas-fired?300,000 and ?2,500,000Thermal EfficiencyAppendix A, Section 2.
Hot WaterGas-fired>2,500,000Combustion EfficiencyAppendix A, Section 3.
Hot WaterOil-fired?300,000 and ?2,500,000Thermal EfficiencyAppendix A, Section 2.
Hot WaterOil-fired>2,500,000Combustion EfficiencyAppendix A, Section 3.
SteamGas-fired (all*)?300,000 and ?2,500,000Thermal EfficiencyAppendix A, Section 2.
SteamGas-fired (all*)>2,500,000 and ?5,000,000Thermal EfficiencyAppendix A, Section 2.
>5,000,000Thermal EfficiencyAppendix A, Section 2.
OR
Appendix A, Section 3 with Section 2.4.3.2.
SteamOil-fired?300,000 and ?2,500,000Thermal EfficiencyAppendix A, Section 2.
SteamOil-fired>2,500,000 and ?5,000,000Thermal EfficiencyAppendix A, Section 2.
>5,000,000Thermal EfficiencyAppendix A, Section 2.
OR
Appendix A, Section 3. with Section 2.4.3.2.

* Equipment classes for commercial packaged boilers as of July 22, 2009 (74 FR 36355) distinguish between gas-fired natural draft and all other gas-fired (except natural draft).

(c) Field Tests. The field test provisions of appendix A may be used only to test a unit of commercial packaged boiler with rated input greater than 5,000,000 Btu/h.

[81 FR 89305, Dec. 9, 2016]