Indiana Code 13-23-5-1. Restrictions on timing of tank installations; tanks for alcohol blended fuels
(1) the tank will prevent releases due to corrosion or structural failure for the operational life of the tank;
(A) cathodically protected against corrosion;
(B) constructed of noncorrosive material;
(C) steel clad with a noncorrosive material; or
(D) designed to prevent the release or threatened release of any stored substance;
(3) the material used in the construction or lining of the tank is compatible with the substance to be stored; and
(4) after July 1, 2007, all newly installed or replaced piping connected to the tank meets the secondary containment requirements adopted by the board.
(b) An underground storage tank system that contains alcohol blended fuels composed of greater than fifteen percent (15%) alcohol may be installed during the period referred to in subsection (a) if the system is otherwise in compliance with rules adopted by the board concerning technical and safety requirements relating to the physical characteristics of underground petroleum storage tanks and ancillary equipment, including dispensing equipment, used in the storing or dispensing of alcohol blended fuels for purposes of all other provisions of this article.
(c) Owners and operators of underground storage tank systems that store, carry, or dispense alcohol blended fuels composed of greater than fifteen percent (15%) alcohol that comply with subsection (b) are considered to meet the standards of:
(1) compatibility under subsection (a)(3); and
(2) compliance for purposes of all other provisions of this article.
[Pre-1996 Recodification Citation: 13-7-20-18(a).]
As added by P.L.1-1996, SEC.13. Amended by P.L.75-2007, SEC.1; P.L.221-2007, SEC.13; P.L.96-2016, SEC.11; P.L.176-2023, SEC.36.