Ask a legal question, get an answer ASAP!
Click here to chat with a lawyer about your rights.

In addition to the requirements specified in section 2 of this act, each unattended terminal at which a tank filled by pipeline is located shall comply with the following requirements:

a. The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within the terminal or at the point of receipt into the aboveground liquid storage tank.

b. The high level alarm system shall be capable of automatically shutting off or diverting the flow of the flammable liquid at the point of origin within the terminal or at the point of receipt into the aboveground liquid storage tank in the event of a power failure in the high level alarm system.

L.1984, c. 31, s. 4, eff. Nov. 1, 1984.