(1) In IMC, Table 403.3.1.1, note “h” is deleted and replaced with the following:

     “h. 1. A nail salon shall provide each manicure station where a nail technician files or shapes an acrylic nail, as defined by rule by the Division of Professional Licensing, in accordance with Title 63G, Chapter 3, Utah Administrative Rulemaking Act, with:

     a. a source capture system equipped with, at minimum, a MERV 8 particulate filter and an activated carbon filter that is capable of filtering and recirculating air to inside space at a rate not less than 50 cfm per station; or

     b. a source capture system capable of exhausting not less than 50 cfm per station.

     c. A nail salon that complies with Note h. la or h. lb is not required to comply with the labeling, listing, or testing requirements described in International Mechanical Code sections 301.7 or 301.8.

     2. For a source capture system described in paragraph 1, the source capture system inlets for exhausting or recirculating air shall be located in accordance with Section 502.20.

     3. Where one or more exhausting source capture systems described in paragraph 1 operate continuously during occupancy, the source capture system exhaust rate shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon.

     4. The requirements of this note apply to:

     a. an existing nail salon that remodels the nail salon after July 1, 2017;

     b. a new nail salon that begins construction after July 1, 2017; and

     c. all nail salons beginning on July 1, 2020.”

Ask a legal question, get an answer ASAP!
Click here to chat with a lawyer about your rights.

Terms Used In Utah Code 15A-3-402

(2) IMC, Section 502.20 is deleted and rewritten as follows:

     “502.20 Manicure stations. A nail salon that files or shapes an acrylic nail shall provide each manicure station with a source capture system in accordance with Table 403.3.1.1, note h. For a manicure table that does not have factory-installed source capture system inlets for recirculating or exhausting air, a nail salon shall provide the manicure table with inlets for recirculating or exhausting air located not more than 12 inches (305 mm) horizontally and vertically from the point of any acrylic chemical application.

     Exception: Section 502.20 applies to a manicure station in:

     a. an existing nail salon that remodels the nail salon after July 1, 2017;

     b. a new nail salon that begins construction after July 1, 2017; and

     c. all nail salons beginning on July 1, 2020.”

(3) In IMC, Section 908.1, the following words are added at the end of the last sentence: “or UL/CSA 60335-2-40.”
(4) In IMC, Section 918.1, the following words are added after “1995”: “or UL/CSA 60335-2-40.”
(5) In IMC, Section 918.2, the following words are added at the end of the sentence: “or UL/CSA 60335-2-40.”
(6) In IMC, Section 1101.6, the following sentence is added at the end of the paragraph: “High probability systems utilizing A2L refrigerants shall comply with ASHRAE 15.”
(7) IMC, Chapter 15 is amended by adding the following referenced standard to CSA:“Standard reference numberTitleReferenced in code section numberCSA: CSA C22.2 60335-2-40-2019Standard for Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers – 3rd EditionM1403.1, M1412.1, M1413.1″
(8) IMC, Chapter 15 is amended by adding the following referenced standard to UL:“Standard reference numberTitleReferenced in code section numberUL: 60335-2-40-2019Standard for Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers – 3rd EditionM1403.1, M1412.1, M1413.1″